Electromagnetic Field and Force Analysis of Three-Phase Enclosure Type GIS Bus Capsule
Keywords:
Eddy currents, electromagnetic forces, finite element methods, GIS, plug-in connector, power loss and short circuitAbstract
With the aim to optimization design and condition monitoring of Gas Insulation Station (GIS), a 3-D finite element model has been developed for the computation of the electromagnetic field and forces in a three-phase enclosure type GIS bus capsule. The calculation takes into account the bus bar connectors’ contact resistance by modeling equivalent contact bridges between contact interfaces and physical properties of the materials involved have also been considered. Using the field distributions, power losses and electromagnetic forces have been calculated, the calculation is more valid and accurate compared to those from closed-formulas. The influence of the operation current and short current on those quantities is also examined. The results show that the distributions of current density and electromagnetic force in the conductors and tank are not uniform. Electromagnetic force of plug-in connector obtained by closed-formulas calculation has obvious deviation, due to the current distributions are not considered. The electromagnetic forces of bus conductors and plug-in connectors are large enough to overcome hold forces exerted by the contact springs under short circuit conditions.
Downloads
References
A. H. Cookson and C. S. Cleale, “Three-conductor compressed gas cable optimization,” EPRI PROJECT 7840 Final Report, February 1979.
J. K. Kim and S. C. Hahn, “Temperature rise prediction of EHV GIS bus bar by coupled magneto-thermal finite element method,” IEEE Trans. Magnetics., vol. 41, no. 5, pp. 1636-1639, 1994.
S. W. Kim, H. H. Kim, and S. C. Hahn, “Coupled finite-element-analytic technique for prediction of temperature rise in power apparatus,” IEEE Trans. Magnetics., vol. 38, no. 2, pp. 921-924, 2002.
D. Labirdis and V. Hatziathanassiou, “Finite element computation of field, forces and inductances in underground SF6 insulated cables using a coupled magneto-thermal formulation,” IEEE Trans. Magnetics., vol. 30, no. 4, pp. 1407- 1415, 1994.
H. K. Kim, J. K. Jung, K. Y. Park, C. H. Im, and H. K. Jung, “Efficient technique for 3-D finite element analysis of skin effect in current-carrying conductors,” IEEE Trans. Magnetics., vol. 40, no. 2, pp. 1326-1329, 2004.
C. T. Liu and S. Y. Yao, “Electromagnetic field and force analyses of a noncontacting conveyance system for steel mill application,” IEEE Trans. Magnetics., vol. 38, no. 5, pp. 3318-3320, 2002.
T. Bauer, W. Mai, and G. Henneberger, “Improved 3D coupled calculations of the structural-dynamic behavior of induction furnaces excited by electromagnetic forces using adaptive algorithms,” IEEE Trans. Magnetics., vol. 36, no. 4, pp. 1565- 1568, 2000.
P. Pellerey, V. Lanfranchi, and G. Friedrich, “Coupled numerical simulation between electromagnetic and structural models, influence of the supply harmonics for synchronous machine vibrations,” IEEE Trans. Magnetics., vol. 48, no. 2, pp. 983-986, 2012.
I. Shokichi, T. Yoshiaki, K. Yoshihiro, and O. Tomohiro, “Numerical analysis of electromagnetic forces in low voltage ac circuit breakers using 3-D finite element method taking into account eddy currents,” IEEE Trans. Magnetics., vol. 34, no. 5, pp. 2597-2600, 1998.
H. Hama, T. Marutani, K. Takatsuka, T. Nitta, and T. Tanabe, “Characteristics of short circuit electromagnetic forces in three phase enclosure type gas insulated bus,” IEEE Trans. Power Delivery, vol. PWRD-2, no. 2, pp. 367-373, 1987.
Y. Kanno, T. Amemiya, N. Takahashi, and N. Kobayahi, “The short circuit electro-magnetic force of the three-phase encapsulated gas insulated bus-bar,” IEEE Trans. Power Apparatus and Systems, vol. PAS-103, no. 6, pp. 1386-1393, 1984.
S. Mon, S. Imai, K. Ninomiya, H. Hata, K. Itaka, and T. Hara, “Characteristics of gas insulated transmission lines bonded at both ends in relation to short-circuit force,” IEEE Trans. Power Apparatus and Systems, vol. PAS-100, no. 5, pp. 2311-2319, 1981.
T. Takeuchi, T. Yoshizawa, and Y. Kuse, “3-D nonlinear transient electromagnetic analysis of short circuit electromagnetic forces in a threephase enclosure-type gas insulated bus,” IEEE Trans. Magnetics, vol. 36, no. 4, pp. 1754-1757, 2000.
K. Yoshihiro, M. Hiroyuki, and I. Shokichi, “3-D finite element analysis of electro-dynamic repulsion forces in stationary electric contacts taking into account asymmetric shape,” IEEE Trans. Magnetics, vol. 33, no. 2, pp. 1994-1999, 1997.
A. E. Emanuel, H. C. Doepken, and P. C. Bolin, “Design and test of a sliding plug-in conductor connector for compressed gas-insulated cables,” IEEE Trans. Power Apparatus and Systems, vol. 95, no. 2, pp. 570-579, 1976.
R. Holm, “Electric contacts, theory and applications,” Springer, New York, 1979.